Issue:
How do I know if I can replace the trip unit in my H, J, or L frame breaker?
Product line:
Molded case circuit breakers
Resolution:
Yes. The breaker needs to have either a T or R suffix after the amperage of the breaker (e.g. HJL36080T or HJL36060TU33X), which indicates they have a field replaceable trip unit.
The H frame electronic trip units are interchangeable among 60, 100, and 150 A. The H frame thermal magnetic trip units are interchangeable among 15-60 A and 70-150 A (ie. a 30 A can be changed to a 40 A, but cannot be changed to a 70 A)
The J frame electronic trip units are 250 A only. The J frame thermal magnetic trip units are interchangeable among 150-250 A.
The L frame trip units are electronic only, and are interchangeable up or down among 250, 400, and 600 A.
How do I know if I can replace the trip unit in my H, J, or L frame breaker?
Product line:
Molded case circuit breakers
Resolution:
Yes. The breaker needs to have either a T or R suffix after the amperage of the breaker (e.g. HJL36080T or HJL36060TU33X), which indicates they have a field replaceable trip unit.
The H frame electronic trip units are interchangeable among 60, 100, and 150 A. The H frame thermal magnetic trip units are interchangeable among 15-60 A and 70-150 A (ie. a 30 A can be changed to a 40 A, but cannot be changed to a 70 A)
The J frame electronic trip units are 250 A only. The J frame thermal magnetic trip units are interchangeable among 150-250 A.
The L frame trip units are electronic only, and are interchangeable up or down among 250, 400, and 600 A.
Released for: Schneider Electric Canada






Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and en expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Center
Find support resources for all your needs, in one place.