How many conductors and wire sizes will the AF2320GETBMB and CF2530GETBMB end tap box accept?

Issue:
Conductors and wire sizes accepted by AF2320GETBMB and CF2530GETBMB

Product Line:
I Line II Busway

Environment:
Wire size accommodation for termination

Cause:
Clarification regarding the minimum and maximum wire size that can be run to terminate to theAF2320GETBMB and CF2530GETBMB end tap boxes

Resolution:
The 2000A End Cable Tap Box will accept (7) 1/0-600kcmil conductors per phase.
The 3000A End Cable Tap Box will accept (10) 1/0-600kcmil conductors per phase and neutral.

This and other Busway  information can be found in the Busway Systems Class 5600 Catalog 5600CT9101

Schneider Electric Canada

Attachment(s)
Busway 2012 Catalog 5600CT9101.pdf [8.75 MB]