What is the overload relay auxilliary contact for the 8536SBO2V02H20S to make it an 8536SBO2V02H21S?

Issue:
Field installing overload relay auxiliary contact

Product Line:
NEMA Contactors and Starters

Environment:
Products sold and used in the United States

Cause:
Field Installing auxiliary alarm contact

Resolution:
The 8536SBO2V02H21S contains a 9065SS020 solid state relay. You can add one 9999AC04 aux contact to the overload to duplicate the factory H21 form.