Resolution:
Begin by wiring the remote start switch or relay for two wire control between terminals P24 and F.
Program the nameplate motor parameters into the following parameters:
| CODE - DESCRIPTION |
| thr - Motor thermal prot. |
| uLu - Motor rated voltage |
| F415 - Motor rated current |
| F417 - Motor rated speed |
Make the following parameter settings:
| CODE - DESCRIPTION | SETTING |
| LL - Low limit frequency | as desired |
| UL - Upper limit freq | 60 |
| Dec - Deceleration ramp time | as desired |
| ACC - Acceleration ramp time | as desired |
| CMOD - Command mode selection | 0 |