How can the ATV212 or ATV21 be set up for start/stop on terminal and ramp to 60 Hz?
Resolution:
Begin by wiring the remote start switch or relay for two wire control between terminals P24 and F.
Program the nameplate motor parameters into the following parameters:
| CODE - DESCRIPTION |
| thr - Motor thermal prot. |
| uLu - Motor rated voltage |
| F415 - Motor rated current |
| F417 - Motor rated speed |
Make the following parameter settings:
| CODE - DESCRIPTION | SETTING |
| LL - Low limit frequency | as desired |
| UL - Upper limit freq | 60 |
| Dec - Deceleration ramp time | as desired |
| ACC - Acceleration ramp time | as desired |
| CMOD - Command mode selection | 0 |
“If this article does not answer your question, check out our FAQ database that has answers to more commonly asked questions:
If this FAQ did not solve your issue, you can call us at 1-888-778-2733 Option 2 and then 4 or e-mail us at drive.products.support@se.com to create a case with our Technical Support Team.