Can the LUCA12BL be controlled with a PLC?
Issue:
The LUCA12BL is to be controlled directly with the output of a PLC.
Product Line:
Tesys U line
Environment:
LUB32+LUCA12BL
Cause:
PLC doing remote control of the motor starter.
Resolution:
Yes, if the output of the PLC is 24 V DC and can handle an inrush of 220mA . A reversing module will add 120mA to the inrush when it has to change the direction of the motor.
The LUCA12BL is to be controlled directly with the output of a PLC.
Product Line:
Tesys U line
Environment:
LUB32+LUCA12BL
Cause:
PLC doing remote control of the motor starter.
Resolution:
Yes, if the output of the PLC is 24 V DC and can handle an inrush of 220mA . A reversing module will add 120mA to the inrush when it has to change the direction of the motor.