Video: How can I obtain run status from ATV212 and S-Flex drives?
You can retrieve the run status from ATV212 and S-Flex drives by wiring to specific terminals and ensuring the correct parameter settings are configured.
ATV212 Open Style Drives
- Connect directly to terminals RYA and RYC.
- Set parameter F130 = 14 (Drive Running).
- When a run command is active, the relay contacts change from normally open to closed.
- The contacts return to open when the run command is removed or if a fault stops the drive.
S-Flex Enclosed Drives (AFC or Bypass Mode)
- Run status is available at terminals 13 and 14 when operating in AFC or Bypass mode.
S-Flex Enclosures (June 2011 and Earlier)
- Use RYA (terminal 11) and RYC (terminal 12) on the drive.
- Set F130 = 14 (Drive Running).
- Contacts close when the drive is running and reopen when stopped or faulted.
- In Bypass mode, run status is also available at terminals 13 and 14.
S-Flex Drives with LON Option Card
- RYA and RYC terminals are not available.
- Run status in AFC mode must be obtained through the network communication system.