What is the difference between primary and secondary injection testing for circuit breakers?

Product Line:
Molded Case Circuit Breakers

Resolution:
Secondary injection testing:

  • Can be done on electronic breakers only
  • Quick
  • Tests the trip unit only
  • Easier
  • Takes less expertise to run the test
  • Test kit is small and portable
  • Less expensive

Primary injection testing:

  • Can be done on thermal magnetic and electronic breakers
  • Time intensive
  • Tests complete breaker from the CT, CT wiring to the trip unit, and the trip unit
  • Takes more expertise to run the test
  • Equipment is heavy and less portable
  • More expensive

Schneider Electric Canada

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:

Need help?

Need help?

Product Selector

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Get a Quote

Start your sales inquiry online and en expert will connect with you.

Where to buy?

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Center

Help Center

Find support resources for all your needs, in one place.

  • Help and Contact Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Product Selectors
  • Software and Firmware
  • Product Substitution and Replacement
  • Blog
  • Events
  • Schneider Electric Community
  • Sustainability
  • Legal Information
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings