How do I calculate the energy savings when using a Constant Torque rated VFD in a Constant Torque Application?

Issue:
Information needed to determine the energy savings for a variable frequency drive (VFD) system in a constant torque application.

Product Line:
All constant torque rated Altivar Drives.

Environment:
All constant torque rated drives, All serial numbers.

Cause:
What is the percentage of energy usage reduction compared to the reduction in speed?

Resolution:
In a constant torque application, The energy used is directly proportional to the speed of the motor.   At 25% speed, 25% energy is used.  At 50% speed, 50% energy is used.  This is different than in variable torque applications where the reduction in power usage is greater than the reduction in speed.

When calculating energy consumption for constant torque applications, The percentage of motor speed is used to determine energy usage.

Schneider Electric Canada

Explore more
Product:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Product:

Need help?

Need help?

Product Selector

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Get a Quote

Start your sales inquiry online and en expert will connect with you.

Where to buy?

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Center

Help Center

Find support resources for all your needs, in one place.

  • Help and Contact Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Product Selectors
  • Software and Firmware
  • Product Substitution and Replacement
  • Blog
  • Events
  • Schneider Electric Community
  • Sustainability
  • Legal Information
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings