Adding Modgate Modbus Devices to ION Enterprise and ION Setup

Product line
Power Monitoring Expert 7.x
Power Monitoring Expert 8.x
Power Monitoring Expert 9.x
Power Monitoring Expert 2020
Power Monitoring Expert 2021
Power Monitoring Expert 2022
Power Monitoring Expert 2023


Issue

A Modbus meter has been connected to an ION7650 or ION7550 serially via RS-485 or RS-232. The ION7x50 meter has been configured with Modgate to communicate to the Modbus device. The user wants to add this device to PME or ION Setup.

Resolution

Ensure both the Modgate meter and the Modbus device have been configured correctly.

1) Open the Management Console and click on the Sites button.

2) Right-click on the open space and select New>Ethernet Gateway Site.

Adding Modgate Modbus Devices to ION Enterprise and ION Setup
3) Enter a Name for the site, and IP Address, and select port 502 as the Port Number.

Adding Modgate Modbus Devices to ION Enterprise and ION Setup

4) Connect to the site.

Adding Modgate Modbus Devices to ION Enterprise and ION Setup

5) Click on the Devices button.

6) Right-click in the open space and select New>Serial Device on the Ethernet Gateway Site.

Adding Modgate Modbus Devices to ION Enterprise and ION Setup

7) Enter device connection information including Group, Name, Device Type, Unit ID, and the Site name created in step 3.
NOTE: If the ION6200 meter is being used as a Modbus device, select the "ION6200 (Modbus)" driver and not the "ION6200" driver.

Adding Modgate Modbus Devices to ION Enterprise and ION Setup

8) Verify device communication by observing real-time data in Vista.


ION Setup

1) Open ION Setup in Network mode.

2) Right-click on the computer name and select Insert Item>Site.

3) Enter the site Name, select Ethernet, and check Gateway. Enter the IP Address of the ION Meter and choose 502 for the Port.
Adding Modgate Modbus Devices to ION Enterprise and ION Setup

4) Right-click on the new site and select Insert Item>Meter.

5) Enter device Name, Type, Unit ID, and Group.

NOTE: If using an ION6200 meter, click on the Display tab and select the correct template.
- Refer to the User Guide for information on how to determine the firmware version.

Adding Modgate Modbus Devices to ION Enterprise and ION Setup
6) View real-time data to confirm communication.


Schneider Electric Canada

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:

Need help?

Need help?

Product Selector

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Get a Quote

Start your sales inquiry online and en expert will connect with you.

Where to buy?

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Center

Help Center

Find support resources for all your needs, in one place.

  • Help and Contact Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Product Selectors
  • Software and Firmware
  • Product Substitution and Replacement
  • Blog
  • Events
  • Schneider Electric Community
  • Sustainability
  • Legal Information
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings