How can we help you today?

How do I read or write a program to/from the SY/MAX model 50 controller to the 8005PR4 hand held programmer?

Issue

How do you I read or write a program to/from SY/MAX model 50 controller to the 8005PR4 hand held programmer?

Product Line

SY/MAX

Environment

80005PR4

Resolution

To read a program from the SY/MAX model 50 controller to the 8005PR4 enter the following sequence:

  1. TRS, READ.
  2. Once "TRS P T L GO?" is displayed make sure the CPU is halted and a memory pack is installed and then press the ENTR key. "TRS P T L" is displayed during execution.
  3. When completed "TRS P T L END" is displayed.


To write a program from the 8005PR4 to the SY/MAX model 50 controller enter the following sequence:

  1. TRS, ENTR.
  2. Once "TRS L T P GO?" is displayed make sure the CPU is halted and either a 8005MP1 or 8005MP4 CMOS RAM memory pack is installed and then press the ENTR key. "TRS L T P" is displayed during execution.
  3. When completed "TRS L T P END" is displayed.

Schneider Electric Canada

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Help and Contact Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Product Selectors
  • Software and Firmware
  • Product Substitution and Replacement
  • Blog
  • Events
  • Schneider Electric Community
  • Sustainability
  • Legal Information
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings