How do I communicate with multiple ION 7600 over ethernet with DNP3.0?

Issue
DNP3.0 requires a unit ID even if it is over ethernet.

Product Line
ION 7500, ION7600

Environment
IONSetup

Cause
The framework in an ION7600 does not allow you to set the DLAddress for ethernet (which is essentially the unit ID).

Resolution

  1. Set COM2 to Ethergate
    Setup assistant
  2. Connect the twisted shielded pair (RS485) between COM1 and COM2
  3. Set the protocol on COM1 to DNP3.0 then set the unit ID to the desired number.
    Setup com protocol
NOTE: all devices and COM ports must have unique device IDs, and all operate at the same baud rate.

Schneider Electric Canada

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:

Need help?

Need help?

Product Selector

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Get a Quote

Start your sales inquiry online and en expert will connect with you.

Where to buy?

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Center

Help Center

Find support resources for all your needs, in one place.

  • Help and Contact Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Product Selectors
  • Software and Firmware
  • Product Substitution and Replacement
  • Blog
  • Events
  • Schneider Electric Community
  • Sustainability
  • Legal Information
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings