How can we help you today?

What is the Excitation (aka Wake up or Minimum Pickup) Current for CM-2000

Issue
User would like to know the minimum current required for CM2000 to measure current

Product
CM2000

Resolution
There must be 25 milliamps on the CT secondary or 0.5% of the CT primary ratio to wake up current readings.

For more information, see detailed datasheet here

Schneider Electric Canada

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Help and Contact Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Product Selectors
  • Software and Firmware
  • Product Substitution and Replacement
  • Blog
  • Events
  • Schneider Electric Community
  • Sustainability
  • Legal Information
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings