Run time error ‘457’ pops up on a client workstation
Goals and Symptoms
Summary
Run time error 457 pops up on a client workstation when using Reporter to edit / create a query Keywords
Symptoms
Reporter runs in the primary server without problems
Reporter crashes with Run time error 457. This key is already associated with an element of this collection when runs on a client machine
Facts and Changes
Keywords
Run time error 457.
This key is already associated with an element of this collection.
Reporter error in client
Reporter error in 5.0
Causes and Fixes
Cause
Primary server has ION Enterprise 5.0 SP4 installed.
Client workstation has ION Enterprise 5.0 with a lower SP.
All of the programs (.exes) and dynamic link libaries (.dlls) are stored locally on client machines, so when repgen is run, it uses the exes and dlls from the machine on which it is run.
When service packs are applied they should run in both primary and client machines.
Resolution
Upgrade the client workstation to the same service pack as the primary server.
If it is possible apply the latest service pack in both computers.
Workaround
Copy the files from the primaryto the client (pmlrepcfg.dll, pmlrepgen.dll, repgen.exe). Note that the dlls should be registered.
More Information
KB article # 10190 Reporter ION Enterprise 5.0 crashes with runtime error 457
Original article#12670 |