RJ or RL PowerPacT breaker with new trip unit installed does not pass primary injection test for ground fault
Issue:
RJ or RL Powerpact breaker is not passing primary injection testing for ground fault.  New trip unit was recently installed.

Product Line:
Powerpact RJ or RL

Resolution:
Do NOT install new trip units in Compact NS1600b–3200 H interrupting rating or PowerPacT RJ/RL circuit breakers with a date code of 09011 or earlier. See A, Figure 1 of attached Micrologic special instruction bulletin 48049-160-01 for location of date code on breaker.

To resolve this issue, reinstall the older trip unit or replace the breaker.

Schneider Electric Canada

Attachment(s)
Micrologic Special Instructions.pdf [679.86 KB]
Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:

Need help?

  • Product Selector

    Quickly and easily find the right products and accessories for your applications.

  • Get a Quote

    Start your sales inquiry online and en expert will connect with you.

  • Where to buy?

    Easily find the nearest Schneider Electric distributor in your location.

  • Help Center

    Find support resources for all your needs, in one place.

  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Find our Offices
  • Get a Quote
  • Where to buy
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Register Your Product
  • Blog
  • Legal Information
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings