RSU or LTU software and UTA (STRV00910) not communicating with Micrologic trip unit
Issue:
RSU or LTU software and UTA (STRV00910) not communicating with Micrologic trip unit

Product Line:
Powerpact H, J and L frame with Micrologic trip unit

Resolution:
Your computer may not be recognizing your new hardware, the UTA test kit in the USB port.

Go into your Windows control panel
Go into the device manager
Right click on Ports (COM & LPT)
Click on "Scan for hardware changes"

Now you should be able to go into your RSU or LTU program
Click on Setup, click on PC communication parameters
For Channel, select USB Maint. Module
For Serial port name, select COM (port number):  Maintenance Module

Schneider Electric Canada

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:

Need help?

  • Product Selector

    Quickly and easily find the right products and accessories for your applications.

  • Get a Quote

    Start your sales inquiry online and en expert will connect with you.

  • Where to buy?

    Easily find the nearest Schneider Electric distributor in your location.

  • Help Center

    Find support resources for all your needs, in one place.

  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Find our Offices
  • Get a Quote
  • Where to buy
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Register Your Product
  • Blog
  • Legal Information
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings