How can we help you today?

What replacement main breaker can be used in the old CSED catalog numbers C200QRF, C200WQRB, C200QRB, C150QRF, C150WQRB, and C150QRB?

Issue:
Product Design Features

Product Line:
CSED

Resolution:
These catalog numbers are all obsolete and no longer available with no repair parts, except for the main breakers.

C200QRF = The original Q2M2200MB main breaker can be replaced with a QBP22220TM.
C200WQRB = The original Q2M2200MB main breaker can be replaced with a QBP22200TM.
C200QRB = The original Q2M2200MB main breaker can be replaced with a QBP22220TM.
C150QRF = The original Q2M2150MB main breaker can be replaced with a QBP22150TM.
C150WQRB = The original Q2M2150MB main breaker can be replaced with a QBP22150TM.
C150QRB = The original Q2M2150MB main breaker can be replaced with a QBP22150TM.