Issue:
Convert a MB NQ442L2C Panel to a Main lug keeping the same MH50 box
Product Line:
NQ Panelboards
Environment:
Conduit piped already into MH 50 box
Cause:
Change from Main breaker to Main lug Panelboard after installation of box
Resolution:
1) Remove the Main breaker kit and install a NQALM2 Main lug kit .
2) Install a 12" rail extension NQ12RDE kit to the Mains end of interior, and use the Blank Deadfront provided in the extension kit to cover Main lugs