Issue
A new protection application type is need for the existing Sepam.

Product Line
Sepam series 20
Sepam series 40
Sepam series 80

Environment
Application Type

Resolution
The answer is a little bit different according to the Sepam series:

  • ​Sepam series 20 and 40: Modification of Sepam application type requires replacement of your complete Sepam. You need to order a new PowerLogic Protection Relay with the correct application type needed.
  • Sepam series 60 and 80: As application type is in the cartridge, modification of Sepam application type requires only replacement of the cartridge. You need to order a new cartridge with the application type needed. Note: be careful, since you may need to purchase additional CCA63x CT adapters, depending on which Application Types are involved.

Note that in all cases, a firmware patch cannot modify application type of a Sepam.

Update Note (April 2026).

The Sepam 20/40 range is obsolete and has been replaced by the PowerLogic P3 / P5 line, depending on the application. Likewise, the Sepam 60/80 range is in the final stage of its commercial life, and for new projects it can be replaced by the PowerLogic P7.

Schneider Electric Canada

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Help and Contact Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Product Selectors
  • Software and Firmware
  • Product Substitution and Replacement
  • Blog
  • Events
  • Schneider Electric Community
  • Sustainability
  • Legal Information
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings