Can the standard full size Homeline branch circuit breakers be used in the new Homeline plug-on neutral load centers?
Issue:
Branch Circuit breakers used in the HOM Plug-On Neutral Load Centers
Cause:
Using standard Homeline branch breakers in PON LCs
Resolution:
Yes, the standard full size Homeline branch breakers can be used in the new Homeline plug-on neutral (PoN) load centers. This would include the old style GFI, AFI, and CAFI breakers with the white neutral pigtail wire (the pigtail wire on these breakers would still be wired to the neutral bar).
NOTE: The new plug-on neutral branch breakers CANNOT be used in the old style non-plug-on neutral Homeline load centers.
Branch Circuit breakers used in the HOM Plug-On Neutral Load Centers
Cause:
Using standard Homeline branch breakers in PON LCs
Resolution:
Yes, the standard full size Homeline branch breakers can be used in the new Homeline plug-on neutral (PoN) load centers. This would include the old style GFI, AFI, and CAFI breakers with the white neutral pigtail wire (the pigtail wire on these breakers would still be wired to the neutral bar).
NOTE: The new plug-on neutral branch breakers CANNOT be used in the old style non-plug-on neutral Homeline load centers.
Released for: Schneider Electric Canada






Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and en expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Center
Find support resources for all your needs, in one place.