Will the ATS22 Display Power Up with Only Control Voltage Applied?
Resolution:
Yes. The ATS22 display should power up when the proper control voltage is applied, even if line power is not present.
If the display does not illuminate, perform the following checks:
- Disconnect any remote HMI that may be connected to the soft starter.
- Measure the control voltage at terminals CL1 and CL2.
- Verify that the measured voltage matches the requirements for your ATS22 model:
- ATS22...S6 and ATS22...Q models: approximately 230 VAC
- ATS22...S6U models: approximately 110 VAC