Can a circuit breaker with a toggle handle be installed in any position?
Issue:
Installing a circuit breaker with toggle handle

Product Line:
All MCCB and MCB circuit breakers with toggle handles

Resolution:
While circuit breakers will function in any position, the NEC places a restriction when vertically mounted, per the following paragraph:

240.81 Indicating. Circuit breakers shall clearly indicate whether they are in the open “off” or closed “on” position.
Where circuit breaker handles are operated vertically rather than rotationally or horizontally, the “up” position of the handle shall be the “on” position.