Can an NQ panel be used on a 240V 3PH Delta system ?
Issue:
NQ panelboards rated for a 240V 3 phase 3 wire delta voltage system

Product Line:
Panelboards

Environment:
NQ

Resolution:
Yes. Branch breakers must be 3P or QO--H / QOB--H and must carry a full 240V rating.
NOTE: This is not the same as a 240D/120VAC 3PH 4W system.