Issue:
NQ panelboards rated for a 240V 3 phase 3 wire delta voltage system
Product Line:
Panelboards
Environment:
NQ
Resolution:
Yes. Branch breakers must be 3P or QO--H / QOB--H and must carry a full 240V rating.
NOTE: This is not the same as a 240D/120VAC 3PH 4W system.