Can GV2 manual motor starters be used with single phase motors?

Issue:
Are the GV2 Manual starters suitable to be used on single phase applications?

Product Line:
IEC Contactors and Starters

Environment:
GV2 Manual motor starters

Cause:
These units show single phase ratings, but are set up for three phase applications

Resolution:
These units need to see current across three poles to operate properly.  If only one or two legs are wired for a single phase application, the unit will trip as it will think that a phase has been dropped.  Thus, either a hot leg or the neutral must be looped through the otherwise unused pole so that all three poles are being used.

Schneider Electric Canada

Explore more
Product:
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Product:
Range:

Need help?

Need help?

Product Selector

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Get a Quote

Start your sales inquiry online and en expert will connect with you.

Where to buy?

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Center

Help Center

Find support resources for all your needs, in one place.

  • Help and Contact Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Product Selectors
  • Software and Firmware
  • Product Substitution and Replacement
  • Blog
  • Events
  • Schneider Electric Community
  • Sustainability
  • Legal Information
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings