How can we help you today?

Why is coil part number 31104-400-50 used for all system voltages?

Issue:
Why is NEMA 6&7 Coil 31104-400-50 used for all system voltages?

Product Line:
NEMA and Definite Purpose Contactors and Starters

Environment:
9998 Magnetic Coils

Resolution:
This coil is used for ALL system voltages, because it is powered and controlled by a control module which develops the DC pickup and DC holding voltages.

Ohms = 3.4 to 4.2 (20°C) - If the coil reads outside this range, the coil should be replaced.

Schneider Electric Canada

Discuss this topic with experts