{}

Our Brands

Impact-Company-Logo-English Black-01-177x54

Welcome to the Schneider Electric Website

Welcome to our website.
Search FAQs
Are electronic trip circuit breakers approved for use on NF or NQ panelboards as main breakers?

Article available in these languages: Spanish

Issue:
Use of a Micrologic electronic trip main or sub-feed circuit breakers in NQ or NF panelboards
Product Line:
Panelboards
Environment:
NF or NQ
Cause:
Electronic breaker application
Resolution:
Only the Micrologic Standard LI or LSI electronic trip unit can be used in NQ and NF panelboards as a main or sub-feed breaker.
The catalog number of the circuit breaker must include "U31X" or "U33X" if electronic trip is desired. The Ammeter and Energy Micrologic trip unit circuit breakers are not permitted to be used.

Please note that thermal-magnetic main and sub-feed circuit breakers are permitted.

Schneider Electric Canada

Explore more
Range:
Articles that might be helpful Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Explore more
Range: