When using more than one ground bar in a QO or Homeline load center, is a jumper wire needed to be connected between the two?
Issue:
Product feature

Product Line:
QO and Homeline Load Center

Resolution:
No jumper wire is required. The ground bars are attached to the load center enclosure with thread forming screws, which will give continuity between the ground bars via the enclosure.