Recommended Torque Values for AC/DC connections for the Conext CL-NA
The models with the fuse holders, 200, 201, 300, 301 use a screw connector on the input to the fuse holder. The recommended torque setting is 3 Nm/ 27 in-lbf. This is listed on page 2-17 as Fuse holder termination screw. The 100 bos uses spring cage clamps and does not require any special torque.
All models use spring cage connectors for the AC side.
Please Note:For the units with fuse holders, we do not provide fuses. Fuses must be selected based on the specific installation.
For calculating the PV fuse rating for a specific PV array installation, refer to the PV panel manufacturer documentation and NEC 690.8 and 690.9 in addition to local electrical installation code. Recommended Fuse: Part number: PV1510F Make: Cooper Bussman Rating:1000 VDC, 15 A.
The models with the fuse holders, 200, 201, 300, 301 use a screw connector on the input to the fuse holder. The recommended torque setting is 3 Nm/ 27 in-lbf. This is listed on page 2-17 as Fuse holder termination screw. The 100 bos uses spring cage clamps and does not require any special torque.
All models use spring cage connectors for the AC side.
Please Note:For the units with fuse holders, we do not provide fuses. Fuses must be selected based on the specific installation.
For calculating the PV fuse rating for a specific PV array installation, refer to the PV panel manufacturer documentation and NEC 690.8 and 690.9 in addition to local electrical installation code. Recommended Fuse: Part number: PV1510F Make: Cooper Bussman Rating:1000 VDC, 15 A.
Released for: Schneider Electric Canada
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and en expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Center
Find support resources for all your needs, in one place.