{}

Our Brands

Impact-Company-Logo-English Black-01-177x54

Welcome to the Schneider Electric Website

Welcome to our website.
Search FAQs
Can QO/QOB 3 pole GFI, EPD or EPE breakers be used on 120 V loads with a shared neutral?
Issue:
Can a 3-Pole GFI, EPD or EPE breaker be used on 120 V loads with a shared neutral?

Product Line:
Miniature Circuit Breakers

Resolution:
No. The 3 pole QO(B) GFI, EPD and EPE breakers do not have a load neutral connection and are only rated for 3p 3w loads. They cannot be used on any load requiring a neutral.

Schneider Electric Canada

Explore more
Range:
Articles that might be helpful Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Explore more
Range: