How long must the signal be applied to the shunt trip on a Masterpact NW breaker?

Issue:
How long must the signal be applied to the shunt trip and shunt close on a Masterpact NW breaker to ensure proper operation?

Product Line:
Circuit Breakers

Resolution:
The breaker requires a shunt trip energization time of 200 ms to ensure that the breaker trip mechanism has completed its cycle and has returned to its starting point. A shorter signal will open or close the breaker, but has the risk of causing the mechanism to hang up and not close with the next close signal. It would close with a second signal however. To prevent operating problems, do not pass the signal through an aux contact (which will open in less than 50 ms). If a PLC is used, ensure the signal duration is 200 ms or more.

Schneider Electric Canada

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:

Need help?

Need help?

Product Selector

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Get a Quote

Start your sales inquiry online and en expert will connect with you.

Where to buy?

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Center

Help Center

Find support resources for all your needs, in one place.

  • Help and Contact Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Product Selectors
  • Software and Firmware
  • Product Substitution and Replacement
  • Blog
  • Events
  • Schneider Electric Community
  • Sustainability
  • Legal Information
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings