How can we help you today?

How to wire properly the positive/negative signal to D0/D1 pin of serial port on M340 or NOM for RS485

Question:
How to wire properly the positive/negative signal to D0/D1 pin of serial port on M340 or NOM for RS485?


Answer:
RS485 is the difference signal, so it makes no sense to indicate positive / negative for D1, D0.
Due to the different convention, customer may came across Data+/Data- or B/A combination of wires.
Just wire the Data+ to D1 or B to D1, remeber that when D1>D0, the logical signal is positive inside while it is negative when D1<D0

Schneider Electric Canada

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Help and Contact Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Product Selectors
  • Software and Firmware
  • Product Substitution and Replacement
  • Blog
  • Events
  • Schneider Electric Community
  • Sustainability
  • Legal Information
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings