Event Notification Module 8.3 with Power Monitoring Expert 8.0 alarms not coming into the monitoring section
Issue
Event Notification Module 8.3 not bringing in Alarms from Power Monitoring Expert 8.0
Product Line
Power Monitoring Expert 8.0
Event Notification Module 8.3
Environment
Monitoring and Diagnostics web interface
Cause
Issue with the Alarms.ENMAlarms.dll in the .../system/bin folder of Power Monitoring Expert
Resolution
*Warning: Take backups of any files prior to modifying them. Ensure the backups are in a location that will not be overwritten (i.e. the Desktop).
- Replace the Alarms.ENMAlarms.dll in the .../system/bin with the one from the attached Hotfix.
- Restart the ENM services by clicking Start -> run -> services.msc
The Services are:
PL Alarm Sentry Host Service
SE Event Gathering Service
SE Event Notification Service
SE Event Logging Service