Can you land (3) 600 kcmil wire / per phase, to a HCP508612N panel ?

Issue:
Can (3) 600 kcmil wire per phase, be terminated in a HCP508612N I Line interior ?

Product Line:
I Line Panelboard

Environment:
Installation

Cause:
Cable size

Resolution:
Yes , (3) 600 kcmil can be landed to the Main lugs. This can be accomplished by removing the bottom endwall of enclosure box and ordering a HC4212DEX(S) surface, or (F) Flush 12" box extension.
This will allow the extra wire bending space, per NEC, needed to land the (3) 600 kcmil wire/phase onto the Main lugs. The lugs are able to provide for (4) 3/0-750kcmil/per phase wires, but wire bending restrictions does not permit (4) 750 kcmil termination, only (4) 500 kcmil wires to be landed .

Schneider Electric Canada

Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more

Need help?

Need help?

Product Selector

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Get a Quote

Start your sales inquiry online and en expert will connect with you.

Where to buy?

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Center

Help Center

Find support resources for all your needs, in one place.

  • Help and Contact Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Product Selectors
  • Software and Firmware
  • Product Substitution and Replacement
  • Blog
  • Events
  • Schneider Electric Community
  • Sustainability
  • Legal Information
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings