Can you land (3) 600 kcmil wire / per phase, to a HCP508612N panel ?
Issue:
Can (3) 600 kcmil wire per phase, be terminated in a HCP508612N I Line interior ?
Product Line:
I Line Panelboard
Environment:
Installation
Cause:
Cable size
Resolution:
Yes , (3) 600 kcmil can be landed to the Main lugs. This can be accomplished by removing the bottom endwall of enclosure box and ordering a HC4212DEX(S) surface, or (F) Flush 12" box extension.
This will allow the extra wire bending space, per NEC, needed to land the (3) 600 kcmil wire/phase onto the Main lugs. The lugs are able to provide for (4) 3/0-750kcmil/per phase wires, but wire bending restrictions does not permit (4) 750 kcmil termination, only (4) 500 kcmil wires to be landed .
Can (3) 600 kcmil wire per phase, be terminated in a HCP508612N I Line interior ?
Product Line:
I Line Panelboard
Environment:
Installation
Cause:
Cable size
Resolution:
Yes , (3) 600 kcmil can be landed to the Main lugs. This can be accomplished by removing the bottom endwall of enclosure box and ordering a HC4212DEX(S) surface, or (F) Flush 12" box extension.
This will allow the extra wire bending space, per NEC, needed to land the (3) 600 kcmil wire/phase onto the Main lugs. The lugs are able to provide for (4) 3/0-750kcmil/per phase wires, but wire bending restrictions does not permit (4) 750 kcmil termination, only (4) 500 kcmil wires to be landed .
Released for: Schneider Electric Canada
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and en expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Center
Find support resources for all your needs, in one place.