How can we help you today?

I cannot see any data on Test Harness Simulator or Master Scada While configuring the data points and if I configure all unlocated variables in the BMXNOR0200H webpage.

Issue:
I cannot see any data on Test Harness Simulator or Master Scada While configuring the data points and if I configure all unlocated variables in the BMXNOR0200H webpage.

Product Line:
BMXNOR0200H

Environment:
All

Resolution:
Check and enabled the Data dictionary option when you program the PLC application.
Otherwise, unlocated variables may not be mapped to RTU data points.
Tools → Project Settings → General → PLC embedded data.



Schneider Electric Canada

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Help and Contact Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Product Selectors
  • Software and Firmware
  • Product Substitution and Replacement
  • Blog
  • Events
  • Schneider Electric Community
  • Sustainability
  • Legal Information
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings