How can we help you today?

What is the purpose of the "FDR Synch" button in the BME NOC's DTM while using M580 HSBY System

In a HSBY system, the FDR servers of the paired BMENOC's are automatically synchronized.
You can remove the auto-synch by disabling this service in the DTM.
If, for some reason, you want to manually re-sync the servers, you can do it by pressing this button.
Note that it will also reactivate the auto-sync, as this is the normally recommended sync mode.

Schneider Electric Canada

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Help and Contact Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Product Selectors
  • Software and Firmware
  • Product Substitution and Replacement
  • Blog
  • Events
  • Schneider Electric Community
  • Sustainability
  • Legal Information
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings