How to manage Data inconsistencies in DDDT type of Advantys equipments used in Unity Pro?

Goals and Symptoms

On some equipment, you can have inconsistencies between data in the DDDT type of Advantys equipment when used in Unity Pro.

Example: STB AHI 8321 Module used in an STB island with STB NIP 2x 1x module.
Image1

Causes and Fixes

This behavior is normal If the data is not 32-bit aligned that means, if the Primary variable (32 bit data) object is not acquiring addresses like 0,4,8,12 etc...then the M580 master aligns them automatically to the Byte array. So it is necessary to plan the island in such a way that the variables falls at a 32-bit boundary.

Another easier solution consists in Configuration Advantys software for each module to add an alignment parameter, this parameter allows to re-align the variables.
Image2

After validation variables become consistent.
Image3


Schneider Electric Canada

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:

Need help?

Need help?

Product Selector

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Get a Quote

Start your sales inquiry online and en expert will connect with you.

Where to buy?

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Center

Help Center

Find support resources for all your needs, in one place.

  • Help and Contact Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Product Selectors
  • Software and Firmware
  • Product Substitution and Replacement
  • Blog
  • Events
  • Schneider Electric Community
  • Sustainability
  • Legal Information
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings