Video: How to manually trip a solid state Motor Logic™ Overload Relay
Issue:
Need to test manually SSOLR 9065

Product line:
NEMA and Definite Purpose Contactors and Starters

Environment:
NEMA Contactors and Starters Accessories 9065

Resolution:
Look on the under side of the unit for an indentation with an exposed opening that has a white plastic piece. Take a small screw driver and lift up that piece moving it to the right. You should hear a click. Check the front of the unit for the trip status indication, it should now indicate that it has been tripped. To reset the unit, press the red reset bar on the front of the overload relay device.

Schneider Electric Canada

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:

Need help?

  • Product Selector

    Quickly and easily find the right products and accessories for your applications.

  • Get a Quote

    Start your sales inquiry online and en expert will connect with you.

  • Where to buy?

    Easily find the nearest Schneider Electric distributor in your location.

  • Help Center

    Find support resources for all your needs, in one place.

  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Find our Offices
  • Get a Quote
  • Where to buy
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Register Your Product
  • Blog
  • Legal Information
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings