How can I tell if my ATV61 or ATV71 drive is in sleep mode? (Low speed timeout active).
Issue:
Identify if an ATV61 or ATV71 drive is in sleep mode
Resolution:
A relay or logic output can not be configured to show this status.
In order to determine if the drive is in sleep mode, you will need to have a serial communication network connected to the drive. Perform a read of parameter LRS3 (Logic address 3252 , 16#0CB4). Bit 9 of this word will indicate whether the drive is asleep or awake. If bit 9 is high, the drive is in sleep mode. If low, the drive is in normal operation mode.
Also note that if the Low speed is set greater than 0Hz, the VFD status is RUN, and the VFD motor frequency is 0Hz, then the VFD is most likely in Sleep mode.
If this article does not answer your question, check out our FAQ database that has answers to more commonly asked questions:
Frequently Asked Questions - Schneider Electric (se.com)
If this FAQ did not solve your issue, you can call us at 1-888-778-2733 Option 2 and then 4 or e-mail us atdrive.products.support@se.comto create a case with our Technical Support Team.
If you are not located in North America, please contact your local Customer Care Center for assistance:
Support | Schneider Electric Global (se.com)