How can we help you today?

Unity Pro : increasing or decreasing the number of %M or %MW lead to wrong values for %I or %IW,


On Modicon Momentum & M340, with PLC using State Ram: increasing or decreasing the number of %M or %MW lead to wrong values for %I or %IW, after a build change.
A rebuild all is manadatory.

The hotfix UnityPro_V110_ HF0323828R fixes the issue on Unity Pro V11

The hotfix UnityPro_V100_ HF0323828R will fix the issue on Unity Pro V10

Schneider Electric Canada

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Help and Contact Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Product Selectors
  • Software and Firmware
  • Product Substitution and Replacement
  • Blog
  • Events
  • Schneider Electric Community
  • Sustainability
  • Legal Information
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings