How to disable CM4000T Flicker alarms

Issue
The user is unable to disable CM4000T’s Flicker alarms in ION Setup. As shown below, the flicker alarms found in the standard alarm setup are not enabled.
Standard Alarm Setup

Product Line
CM4000T

Environment
ION Setup

Cause
The Power Quality Summary Configuration forces Flicker alarms to stay enabled

Resolution
Navigate to the Power Quality folder after selecting your CM4000T in ION Setup.
The Power Quality Summary Configuration option needs to be disabled in the CM4000T to restrict Flicker alarms.
Power Quality Summary Configuration

After it is disabled, Flicker alarms will be disabled.
PQ Summary

Schneider Electric Canada

Explore more
Product:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Product:

Need help?

Need help?

Product Selector

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Get a Quote

Start your sales inquiry online and en expert will connect with you.

Where to buy?

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Center

Help Center

Find support resources for all your needs, in one place.

  • Help and Contact Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Product Selectors
  • Software and Firmware
  • Product Substitution and Replacement
  • Blog
  • Events
  • Schneider Electric Community
  • Sustainability
  • Legal Information
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings