Will VR breakers interrupt 5 amps and below chop current?
Issue:
Will VR breakers interrupt 5 amps and below chop current?
Product Line:
Metal Clad
Environment:
Application
Cause:
Can disregard SPD protection
Resolution:
The average chop current for copper-chromium contacts used in VR breakers is about 3 to 3.5 amps and the maximum is about 5 amps"
Will VR breakers interrupt 5 amps and below chop current?
Product Line:
Metal Clad
Environment:
Application
Cause:
Can disregard SPD protection
Resolution:
The average chop current for copper-chromium contacts used in VR breakers is about 3 to 3.5 amps and the maximum is about 5 amps"
Released for: Schneider Electric Canada
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and en expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Center
Find support resources for all your needs, in one place.