{}

Our Brands

Impact-Company-Logo-English Black-01-177x54

Welcome to the Schneider Electric Website

Welcome to our website.
Search FAQs
How to wire a DC motor load to an LC1D contactor
Issue:
Wiring diagram in MKTED210011EN catalog shows what looks to be a resister in line with the series winding of poles for DC5 circuits. Is this representing a resistor and how is this value calculated?

Product Line:
Contactors and Starter - IEC

Environment:
Tesys D

Resolution:
There is no resistor. The rectangle you see in the power wiring diagram is the load ( motor). The DC load could also be non-motor.
This represents that the motor(load) needs to have a contact on each side so there is no voltage present when the contactor is off, and that the air gap is additive no matter which side of the motor the contact is on.

Note: The TeSys D contactors are rated for DC applications but are not UL listed / approved for DC applications.

Schneider Electric Canada

Explore more
Range:
Articles that might be helpful Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Explore more
Range: