When testing with the FFTK, the trip indication on a Micrologic 6.0A/P/H trip unit is Ig, regardless of the function being tested

Issue:
Full function test kit shows ground fault regardless of the test being performed

Product Line:
Molded Case and Air Circuit Breakers

Resolution:
This is because of the way the FFTK tests the trip unit. The FFTK detects a trip by the drop in supply voltage (since the trip unit diverts it all to the trip solenoid). With PI testing, as with in-service, when the breaker trips, the signal goes away and the indication is correct. But with the FFTK, the test signal can still be applied after the trip unit initially sends the trip signal causing multiple protection functions to react. The Ig light is last to react and therefore is the light that is latched on.
If the FFTK says the breaker passes, it passes.

Schneider Electric Canada

Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more

Need help?

Need help?

Product Selector

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Get a Quote

Start your sales inquiry online and en expert will connect with you.

Where to buy?

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Center

Help Center

Find support resources for all your needs, in one place.

  • Help and Contact Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Product Selectors
  • Software and Firmware
  • Product Substitution and Replacement
  • Blog
  • Events
  • Schneider Electric Community
  • Sustainability
  • Legal Information
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings