Question:
How to correct the system error code: 3008 in Scadapack ES?
Answer:
The Status point in the 5000 series I/O is not being validated by the E-series configurator software.
The problem was the status point that was assigned is already been used ( see point address in points folder) causing the system error 3008.
To correct the problem, disable the Stat. Pt. (see details below) or assign a stat point number that was not used.
How to correct the system error code: 3008 in Scadapack ES?
Answer:
The Status point in the 5000 series I/O is not being validated by the E-series configurator software.
The problem was the status point that was assigned is already been used ( see point address in points folder) causing the system error 3008.
To correct the problem, disable the Stat. Pt. (see details below) or assign a stat point number that was not used.
Released for: Schneider Electric Canada
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and en expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Center
Find support resources for all your needs, in one place.