Software Protection Failure. No key found or no license available from network.

Issue
Scada server was rebooted after Windows Updates were applied.

Once the Scada project runs, the following message appears and none of the devices are communicating:

image

Product Line
PowerLogic Scada (all versions)
PowerSCADA Expert (all versions)

Environment
Scada Runtime Manager

Cause
While there are several reasons, in this case the problem was that the server IP address did not match the IP address assigned in Scada project.
Running Computer Setup Wizard on the server, indicated that the server role could only be a Client machine.  A correct project setting would have Server and Control Client enabled and selected.

image

Resolution
In Citect Project Editor select Network Addresses (Servers menu).  Assign an IP address that matches the server IP address.  If server has multiple NIC cards, each IP Address assigned to a NIC Card needs to be added seperately to the project. Compile and run the project.

NOTE: Assigning a static IP address to the server would eliminate future modifications as the server IP address remains constant and not change in case the server is rebooted.

Schneider Electric Canada

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Help and Contact Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Product Selectors
  • Software and Firmware
  • Product Substitution and Replacement
  • Blog
  • Events
  • Schneider Electric Community
  • Sustainability
  • Legal Information
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings