How do you set up preset speeds on the Altivar 630 Process drive using the Somove Software?

Issue:
Can I use SoMove to set up preset speeds on the ATV630 drive?

Resolution:

  1. Open Somove file

First option:

  1. Go to Parameter Layout
  2. Preset Speeds
  3. PS2, assign to a Digital Input
  4. SP2 set to the desired speed.

Second option:

  1. Go to Parameters List
  2. Generic Functions
  3. Preset speeds
  4. PS2, assign to a Digital Input
  5. SP2 set to the desired speed.

You can assign up to 16 Preset Speeds depending on the truth table below:

truth table preset speeds

If this article does not answer your question, check out our FAQ database that has answers to more commonly asked questions:

Frequently Asked Questions - Schneider Electric (se.com)

If this FAQ did not solve your issue, you can call us at 1-888-778-2733 Option 2 and then 4 or e-mail us atdrive.products.support@se.comto create a case with our Technical Support Team.

If you are not located in North America, please contact your local Customer Care Center for assistance:

Support | Schneider Electric Global (se.com)

Schneider Electric Canada

Attachment(s)
servlet.jpeg [65.34 KB]
Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Help Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Product Selectors
  • Software and Firmware
  • Product Substitution and Replacement
  • Blog
  • Events
  • Schneider Electric Community
  • Sustainability
  • Legal Information
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings
  • Preference Center