How can we help you today?

Video: How to install a shunt trip or undervoltage trip on a PowerPacT B frame breaker

Issue:
How to install shunt trip or under voltage trip on a PowerPacT B-frame breaker

Product Line:
PowerPacT Molded Case Circuit Breakers

Resolution:
First, the breaker must be in the tripped position. Once in the tripped position, open the accessory cover and install the shunt or undervoltage in the left slot in the breaker. Push down until it clicks into place. When the cover is closed, the MN (undervoltage) or MX (shunt) green tab will be visible through the window. To remove the shunt or under voltage, take a thin object like a screwdriver, slide into the slot in the device, and push it up until it clicks out of place. For further instruction, see video below:

Schneider Electric Canada

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:

Need help?

Need help?

Product Selector

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Get a Quote

Start your sales inquiry online and en expert will connect with you.

Where to buy?

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Center

Help Center

Find support resources for all your needs, in one place.

  • Help and Contact Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Product Selectors
  • Software and Firmware
  • Product Substitution and Replacement
  • Blog
  • Events
  • Schneider Electric Community
  • Sustainability
  • Legal Information
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings