How can we help you today?

ENM is not receiving PowerSCADA Expert alarms (PSE 8.x)

Product Line
Event Notification Module 8.3 (ENM 8.3)
PowerScada Expert 8.x (PSE 8.x)

Environment
Monitoring and Diagnostics in ENM

Cause
The server IP address has changed.  The change was also applied in Project Editor > Servers > Network Addresses.

Resolution
In a previous instance, the issue was found to be within the Application Configuration Utility.  The Application Services Host was referencing the existing IP address.  Update the existing IP address in Application Services Host > Citect Data Platform > Citect I/O Server Address to correct the issue. This will allow Application Services Host to connect to CTAPI on the correct IP Address.


Application Services Host

Schneider Electric Canada

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:

Need help?

Need help?

Product Selector

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Get a Quote

Start your sales inquiry online and en expert will connect with you.

Where to buy?

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Center

Help Center

Find support resources for all your needs, in one place.

  • Help and Contact Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Product Selectors
  • Software and Firmware
  • Product Substitution and Replacement
  • Blog
  • Events
  • Schneider Electric Community
  • Sustainability
  • Legal Information
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings