What method of ground fault testing is recommended for circuit breakers?

Issue:
Ground fault testing of circuit breakers

Product Line:
Circuit Breakers

Resolution:
Schneider Electric recommends primary injection testing to comply with the requirements of NEC 230.95(C) for ground fault testing upon installation. Secondary injection testing may be done at the option of the customer for scheduled maintenance after the installation has been tested and commissioned.
For test procedures, please consult the Field Test and Maintenance Guide.