How to troubleshoot a closed breaker that has voltage on the line side but low or no voltage on the load side

Issue:
A breaker shows no continuity when tested with an ohmmeter.

Product Line:
MCCB's

Resolution:
All contacts have a minimum voltage and current required before they will conduct. Usually this number is low enough so there is no problem with reading open circuit voltage on an energized breaker with no load, but on rare occasions, the open circuit voltage on the load side will be reduced or prevented by resistive films on the contacts. This film comes mostly from oxidation, but could contain other contaminants as well.

When this is the case, the solution is to put some load on the breaker, as then the current flow driven by line voltage will burn through the resistive film and the breaker will conduct and act normally from then on. The amount of load required depends on the amount of resistance, but a low to moderate load should be enough. It may also be helpful to toggle the breaker, as doing so will reseat the contacts and help break through the resistance.

If there is still no continuity, the breaker may be bad.

Schneider Electric Canada

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:

Need help?

Need help?

Product Selector

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Get a Quote

Start your sales inquiry online and en expert will connect with you.

Where to buy?

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Center

Help Center

Find support resources for all your needs, in one place.

  • Help and Contact Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Product Selectors
  • Software and Firmware
  • Product Substitution and Replacement
  • Blog
  • Events
  • Schneider Electric Community
  • Sustainability
  • Legal Information
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings